LifeSafety Power FPO150/250-2C8P2D8PE8S SWH 16-Door Auxiliary Class II Distribution Outputs Access Control Power Supply in UL Listed Indoor, 30" x36" x6.5" D Enclosure
LifeSafety Power FPO150/250-2C8P2D8PE8S SWH 16-Door Auxiliary Class II Distribution Outputs Access Control Power Supply in UL Listed Indoor, 30" x36" x6.5" D Enclosure
LifeSafety Power FPO150/250-2C8P2D8PE8S SWH 16-Door Auxiliary Class II Distribution Outputs Access Control Power Supply in UL Listed Indoor, 30" x36" x6.5" D Enclosure
FPO150/250-2C8P2D8PE8S | J7-1252CDP8S
Veuillez vous connecter pour voir les tarifs, consulter la disponibilité des produits et ajouter des articles à votre panier.
Aperçu
SCLASS Unified Power Systems are engineered to house FlexPower power modules alongside SWH iSTAR access hardware in one compact listed enclosure. This unit is a 12V and 24V DC dual voltage control access power system.
Two C8 control modules provide sixteen access control inputs capable of voltage or dry contact activation, and sixteen outputs programmable for failsafe / failsecure operation at either 12 or 24 VDC and controlled by the integrated fire alarm interface circuit on the FPO. Two D8 modules provide sixteen auxiliary outputs and each output is configurable for 12 or 24VDC operation.
Specifications
Input Power
- Input 120/230 VAC 50/60 Hz | 452 Watts
- Overload and short circuit protection
- Over temperature protection
- Polarized AC power supply disconnect
Output Power
- FPO150: 12V/12A or 24V/6A | 150 Watts
- FPO250: 12V/20A or 24V/10A | 250 Watts
- Outputs: Continuous (DC1) Resettable (DC2)
- 16 lock control lock outputs, fused at 3A each
- 16 auxiliary outputs, fused at 3A each
- 120 mV output voltage ripple
- System Efficiency: 87% | System BTU Rating: 175 BTU/Hr
Battery Charging
- Independent built-in 2A charger for sealed lead acid or gel type batteries
- Microprocessor dual rate charging of 12 or 24 V battery sets
- Charges up to 80Ah battery sets within UL limit
- Automatic switchover to standby battery when AC fails
- Zero voltage drop when switched over to battery backup
Supervision
- AC Fail (form "C" contacts)
- System Fault (form "C" contacts) may be triggered by low/no battery, short to earth ground, power supply failure or blown fuse
Visual Indicators
- AC input, DC1 and DC2 output
- System fault | AC fault | Short to earth ground | Reverse battery polarity
- Fire Alarm Input activated
- D8: DC outputs
- C8: DC outputs and fault
Regulatory Compliance
- UL294, UL603, UL1076
- ULC S318, ULC S319, CSA C22.2 #107.1, CSA C22.2 #60950
- CE | FCC Part 15, Subpart B | CSFM Approved
Enclosure Dimensions
- Size: 36.00H x 30.00W x 4.50D in. (91.00 x 76.00 x 11.50 cm)
Access Mounting
- SWH Pro or ULTRA Controllers
Principales caractéristiques
Renseignements généraux
Spécifications
ADI Numéro du produit J7-1252CDP8S Code fabricant FPO150/250-2C8P2D8PE8S Genre du connecteur Access Control Marque LifeSafety Power Type de produit Power Supply
Tension de sortie 12V DC, 24V DC
Facteur de forme Enclosure Hauteur 36" Largeur 30" Profondeur 6.5"
Puissance de sortie 400 W Tension d'entrée 120V AC, 230V AC
Pays d'origine US